Question#1

The UPS vendor is offering the latest model of their UPS to you. The vendor indicates that the UPS is categorized as VFD class.
Is this UPS a fit for your mission-critical data centre?

A. Yes
B. No
C. Yes, but only if you oversize the battery bank with 10%.
D. Yes, but only if they install it with a 12-pulse rectifier.

Explanation:
A UPS (uninterruptible power supply) that is categorized as VFD class is not a fit for your mission-critical data centre, because it does not provide adequate protection against voltage and frequency variations. VFD stands for Voltage and Frequency Dependent, which means that the output voltage and frequency of the UPS depend on the input voltage and frequency. VFD UPSs are also known as offline, standby, or line-interactive UPSs. They typically switch to battery power only when the input power fails or goes beyond a certain threshold. However, this switching may cause a brief interruption or a transient in the output power, which can affect the performance and reliability of the ICT equipment. Moreover, VFD UPSs do not filter or regulate the input power, which means that they pass on any voltage or frequency fluctuations, harmonics, or noise to the output power. These power quality issues can also damage or degrade the ICT equipment and the data.
For your mission-critical data centre, you need a UPS that is categorized as VFI class, which stands for Voltage and Frequency Independent. VFI UPSs are also known as online, continuous, or double-conversion UPSs. They provide a constant and clean output power that is independent of the input power. VFI UPSs convert the input AC power to DC power, and then convert it back to AC power with the desired voltage and frequency. This double conversion process isolates the output power from the input power, and eliminates any power quality issues. VFI UPSs also have zero switching time, which means that they do not cause any interruption or transient in the output power when switching to battery power. VFI UPSs are designed to protect the ICT equipment and the data from any adverse effects of voltage and frequency variations, and to ensure the highest level of availability and reliability.
Reference: 1: CDCP Preparation Guide, page 17, section 2.3.1 2: Understanding UPS Classification: Fuji Electric’s Technical Guide3, page 1, section 1 4: Uninterruptible Power Supplies Key Product Criteria5, page 1, section 1 6: UPS Function: Reduced Input Voltage for VFDs - KEB7, page 1, section 1

Question#2

Which one of the following is used in Measuring Business Value?

A. Regeneration Cost
B. Scalability
C. Reliability
D. Upfront Cost

Explanation:
Measuring business value is the process of assessing the benefits and costs of IT investments and initiatives in relation to the strategic objectives and priorities of the organization. One of the factors that can be used to measure business value is scalability, which is the ability of a system or component to handle increasing workloads or demands without compromising performance, quality, or functionality. Scalability is important for business value because it enables the organization to adapt to changing market conditions, customer expectations, and growth opportunities. Scalability can also reduce operational costs, increase efficiency, and improve customer satisfaction. Therefore, scalability is one of the factors that can be used in measuring business value.
Reference:
• EPI Data Centre Training Framework1
• EPI Data Centre Competence Framework2
• Measuring the Business Value of IT3
• How to Measure the Business Value with Effective Data Quality Governance
• 7 Rules for Demonstrating the Business Value of IT

Question#3

is the arithmetic mean of time between the failing and the subsequent running of the system in a particular time period.

A. MTBF
B. MCBF
C. MLBF
D. MTTR

Explanation:
MTBF stands for Mean Time Between Failures, and it is the arithmetic mean of time between the failing and the subsequent running of the system in a particular time period. MTBF is a measure of reliability that indicates how often a system or component fails during its operation. MTBF can be calculated by dividing the total operating time by the number of failures over a given period.
For example, if a system operates for 1000 hours and experiences 5 failures, the MTBF is 1000/5 = 200 hours.
Reference: EPI Data Centre Training Framework, CDCP Preparation Guide, MTBF, MTTR, MTTF, MTTA:
Understanding incident metrics - Atlassian

Question#4

Which Class of Fire involves combustible metals or combustible metal alloys such as magnesium, sodium and potassium?

A. Class A
B. Class B
C. Class C
D. Class D

Explanation:
Class D fires involve combustible metals or combustible metal alloys such as magnesium, sodium and potassium. These metals can react violently with water, air, or other chemicals, and require special extinguishing agents1
Reference: 1: EPI Data Centre Professional (CDCP®) Reference Materials, page 16.

Question#5

An optical fiber cable comes with the specifications 50/125 um.
What do the numbers represent?

A. The first number represents the distance for a 10 Gb/s connection; the second number represents the distance for a 1 Gb/s connection.
B. The first number represents the diameter of the core; the second number represents the diameter of the cladding in microns.
C. The first number represents the diameter of the core; the second number represents the actual diameter cable including the buffer and jacket.
D. The first number represents the required distance to single-phase power cabling; the second number represents the required distance to three-phase cabling.

Explanation:
Optical fiber cables are composed of a core, a cladding, and a coating. The core is the central part of the fiber that carries the light signal. The cladding is the layer surrounding the core that reflects the light back into the core and prevents signal loss. The coating is the protective layer that covers the cladding and provides mechanical strength and environmental protection. The specifications of an optical fiber cable indicate the dimensions of the core and the cladding in microns (μm), which are one millionth of a meter. For example, a 50/125 μm cable has a core diameter of 50 μm and a cladding diameter of 125 μm. The coating diameter is usually 250 μm, but it is not part of the specifications.
Reference: Multimode Optical Fiber Selection & Specification - Corning, Optical Fiber OM3 (50/125µm Multimode Fiber), 50/125 Graded-Index OM2 Optical Fiber - OFS

Exam Code: Exin-CDCP
Q & A: 88 Q&As         Updated:  Oct 17,2026

 

 Access Complete Exin-CDCP Preparation Material

What This Exin-CDCP Study Resource Helps You Do

Review Key Concepts

Review the technologies, products, processes, and practical skills covered by the current Exin-CDCP exam objectives.

Practice Scenario-Based Questions

Work through independently developed questions designed to strengthen your understanding of technical scenarios and decision-making.

Identify Knowledge Gaps

Use your results and the provided explanations to find weaker areas and focus your study more effectively.

How to Use This Exin-CDCP Preparation Material

Review the Exam Scope

Start by reviewing the topics covered by the Exin-CDCP exam. Compare them with the official exam objectives to understand the required technologies, operational tasks, and practical skills, then identify the areas that deserve the most attention.

Practice Independently

Complete a focused set of practice questions for each topic. On your first attempt, avoid referring to notes, answers, or other study resources so that you can evaluate your current understanding more accurately.

Study the Explanations

Review the answers and explanations after completing each practice session. Understand why the correct option is appropriate for the given scenario and why the other options may be incorrect or less suitable.

Close Knowledge Gaps

Keep track of incorrect answers, unfamiliar concepts, and weaker knowledge areas. Review these topics using official documentation and practical experience, then answer the related questions again to reinforce your understanding and monitor your progress.

Independent Exin-CDCP Preparation Resource

CertQueen independently develops its certification study materials for educational purposes. The practice questions are not copied from, recalled from, or presented as live or official exam questions.

CertQueen is not affiliated with, endorsed by, sponsored by, or authorized by any certification provider. Certification names, exam codes, product names, and related trademarks are the property of their respective owners and are referenced only for identification and educational purposes.